Residual Current Circuit Breaker B-Type 4-Poles 63A 300mA 230/400V IP20 Malmbergs 2160543
All-current sensitive residual current circuit breaker that can handle all types of fault currents, containing mixed frequencies from 0-1000 Hz.
Watch this product and we will notify you once it is back in stock.
Residual Current Circuit Breaker B-Type 4-Poles 63A 300mA 230/400V IP20 Malmbergs 2160543
Description
All-current sensitive residual current circuit breaker of type B that can handle all types of fault currents: pure alternating current, smoothed pulsating direct current and pure direct current. Also handles currents containing mixed frequencies from 0 to 1000Hz. Type B is prescribed in, among other things, the following types of installations: charging stations for electric vehicles, frequency converters, UPS, welding, escalators, elevators, etc. Installations that generate fault currents with direct current above 6mA make a regular residual current circuit breaker of type A completely ineffective and will not trip. The RCD is not intended for pure DC systems or AC systems with frequencies other than 50Hz.
Specifications
- Connection: Screw, PZ2
- Connection area: 1-35 mm². Neutral on the left.
- Energy limitation class: 3
- Frequency: 50Hz
- Protection class: IP20
- Rated breaking capacity (Im): 1000A
- Rated short-circuit current: 10kA
- Rated current: 63A
- Number of poles: 4
- Voltage: 230/400V
- Impact voltage withstand, Uimp: 4kV
- Impact current proof: 3kA at 8/20µs
- Temperature range: -25°C – +55°C
- Type: B
- Tripping current: 300 mA
- Tightening torque: 2.5Nm