Personal Protection Circuit Breaker 1-Pole With Neutral Type A 30mA 16A Hager
Personal protection circuit breaker type A, characteristic C with screw connection, supply conductor can be connected from the top or bottom.
Watch this product and we will notify you once it is back in stock.
Personal Protection Circuit Breaker 1-Pole With Neutral Type A 30mA 16A Hager
Description
Personal protection circuit breaker type A, characteristic C with screw connection. A personal protection circuit breaker is an earth-fault circuit interrupter with built-in overcurrent protection that is located in a miniature circuit breaker, which saves space and gives the user an easier overview. The personal protection circuit breaker is in accordance with standard EN 61009-1. Supply conductor can be connected from the top or bottom. If a component on the DIN rail becomes necessary, this can be done without affecting anything other than the product in question. The space-saving (2 modules) personal protection circuit breaker is advantageously used for personal and short-circuit protection of 1-phase outlet groups. The phase rail connection makes it possible to connect more personal protection circuits on the same DIN rail.
Technical Information
- Ambient temperature during operation: -25-40 °C
- Overvoltage category: 3
- Pollution degree: 2
- Rated insulation voltage: 500 V
- Rated short-circuit capacity lcn (EN 61009-1): 6 kA
- Rated short-circuit breaking capacity IEC 60947-2: 6 kA
- Number of poles (total): 2
- Installation depth: 68 mm
- Rated current: 16 A
- Rated impulse protection voltage Uimp: 4 kV
- Current limitation class: 3
- Rated surge current capacity: 0.25 kA
- Rated fault current: 0.03 A
- Connectable conductor area, stranded: 1-16 mm²
- Width in number of module spaces: 2
- Number of fused poles: 1
- Connectable conductor area, solid: 1-25 mm²
- Rated voltage: 240 V
- Protection class (IP): IP20
- Tripping characteristic: C
- Breaking characteristic: Non-delayed
- Voltage type: AC
- Leakage current type: A
- Frequency: 50 Hz
Specifications
- Flush mounting: Yes
- REACH Date: 2022-03-11
- REACH - Contains candidate substances: Lead
- REACH Information obligation: Yes
- Parallel switching neutral conductor: Yes